HP 20cp Instrukcja Instalacji

Przeglądaj online lub pobierz Instrukcja Instalacji dla Osuszacze HP 20cp. HP 20cp Setup and Install Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj

Podsumowanie treści

Strona 1 - (20 ft)

HP Performance-Optimized Datacenter, 6 m (20 ft) Site Requirements Information Part Number 587017-002 March 2010 (Second Edition)

Strona 2 - Intended audience

HP POD specifications 10 Top view Item Component 1 Heat exchanger access panels Water input side view Item Component 1 CWR/CWS portal 2 Ce

Strona 3 - Contents

HP POD specifications 11 Double door end view Item Component 1 IT cable portals External cold aisle view Item Component 1 Fire suppression

Strona 4 - Site requirements

HP POD specifications 12 External hot aisle view Callout Feature 1 Main input power A and B feeds 2 Controlled access keypad (optional) Inter

Strona 5 - System utilities

HP POD specifications 13 Control cabinet interior Item Component 1 Access control system components 2 Fire alarm/fire suppression system compon

Strona 6 - Drainage

HP POD specifications 14 Item Component 7 Fan sequencers 8 Fan power relays 9 Redundant power relays 10 EPO controls and indicators Water sup

Strona 7 - Environmental specifications

Water quality requirements 15 Water quality requirements Water quality requirements and specifications • Closed-loop water must not contain any lim

Strona 8 - Lightning protection

Water quality requirements 16 Piping materials Do not use the following interconnecting piping materials in a closed water system: • Oxidizing bioc

Strona 9 - HP POD specifications

Power management 17 Power management Connection requirements When determining the final location of your power and water connections, consider the d

Strona 10

Power management 18 Item Component 1 Main input power side B lugs and breakers, located behind dead front panels. 2 Main input power side A lugs a

Strona 11

Supported facility connections 19 Supported facility connections Humidifier specifications A dedicated supply of domestic water is required if the o

Strona 12 - Internal components

© Copyright 2009, 2010 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warr

Strona 13

Supported facility connections 20 Functional and supplementary grounding straps are provided between each rack and HP POD. IMPORTANT: Before ins

Strona 14 - Water supply specifications

Supported facility connections 21 Fire, safety, and security notifications Dry contacts are provided to enable the connection between the fire alarm

Strona 15 - Water quality requirements

Acronyms and abbreviations 22 Acronyms and abbreviations ASSD air sampling smoke detector BMS building management system ECS environmental control

Strona 16 - Condensation management

Contents Site requirements ...

Strona 17 - Power management

Site requirements 4 Site requirements About this document This document outlines the installation requirements for a 6 m (20 ft) HP POD. These guide

Strona 18 - Main input power details

Site requirements 5 • You have chilled water at your final location. • You have made provisions for properly grounding the HP POD. System utiliti

Strona 19 - Humidifier specifications

Site requirements 6 Item Component 1 Main input power junction boxes 2 IT cable portals Drainage

Strona 20 - HP POD security

Site requirements 7 Drain hot aisle view Item Component 1 Water main supply/return drains 2 Heat exchanger condensate drain Optional connecti

Strona 21

Site requirements 8 Features Specifications Nonoperating temperature* -29ºC to 54ºC (-20ºF to 130ºF) Operating humidity • 0% to 100% relative nonc

Strona 22 - Acronyms and abbreviations

HP POD specifications 9 HP POD specifications Dimensions The HP POD is approximately 6.7 m (22 ft) long, 2.4 m (8 ft) wide, and 3.1 m (10 ft) tall.

Komentarze do niniejszej Instrukcji

Brak uwag