HP Performance Optimized Datacenter 40c G2
Maintenance and Service Guide
Abstract
This guide provides maintenance and service guidance for the HP Performance Optimized Datacenter 40c (HP POD 40c G2).
Part Number: 695161-001
August 2012
Edition: 1
Przeglądanie stron 0
1 2 3 4 5 6 ... 81 82

Podsumowanie treści

Strona 1

HP Performance Optimized Datacenter 40c G2 Maintenance and Service Guide Abstract This guide provides maintenance and service guidance for the HP Pe

Strona 2

Illustrated parts catalog 10 Electrical panels WARNING: To avoid the risk of personal injury or loss of life, all personnel must comply with PPE

Strona 3 - Contents

Illustrated parts catalog 11 End view shown Cooling system component identification The heat exchanger access hatches are located on top of the PO

Strona 4 - Contents 4

Illustrated parts catalog 12 CAUTION: If any racks contain empty RU space, use the HP POD 40c G2 filler panels to maintain the efficiency of the H

Strona 5 - Contents 5

Illustrated parts catalog 13 Spare part number Description 637138-001 EPO switch cover w/ horn 637139-001 EPO BUTTON 637140-001 ELECTRIC VALVE ACTU

Strona 6 - Illustrated parts catalog

Illustrated parts catalog 14 The spare parts in the following table must be replaced by a licensed fire safety contractor. IMPORTANT: These part

Strona 7 - Illustrated parts catalog 7

Removal and replacement procedures 15 Removal and replacement procedures Safety considerations The HP POD 40c G2 is listed to the UL 69050 standard

Strona 8

Removal and replacement procedures 16 The HP standard suppression system includes a Novec 1230 clean agent system. However, if the customer or local

Strona 9 - Power feeders

Removal and replacement procedures 17 2. Pull the filter down through the frame channels to remove the filter. Replacing the air filter 1. Angle

Strona 10 - Electrical panels

Removal and replacement procedures 18 Busway drop box The internal electrical busways provide a location to connect each of the drop boxes, which th

Strona 11 - HP POD 40c G2 racks

Removal and replacement procedures 19 4. Slide the hardware bracket to the right along the busway, completely disconnecting it from the busway drop

Strona 12 - Replaceable spare parts

© Copyright 2012 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties

Strona 13

Removal and replacement procedures 20 4. Secure the busway drop box to the retaining hardware bracket by using a socket wrench to insert and tighten

Strona 14 - Smoke detector

Removal and replacement procedures 21 Removing the differential pressure sensor 1. Label the pressure sensor tube connection locations, and then re

Strona 15 - Safety considerations

Removal and replacement procedures 22 Door position contact Door position contacts are located on all doors and cabinets. You need a Phillips-head s

Strona 16 - Air filter

Removal and replacement procedures 23 Drain pan sensor The HP POD 40c G2 includes six heat exchanger condensate drains. One drain pan sensor is loca

Strona 17 - Replacing the air filter

Removal and replacement procedures 24 3. Pull the wire through from the satellite box to the sensor location, and then remove the sensor. Heat excha

Strona 18 - Busway drop box

Removal and replacement procedures 25 Header drain pan sensor 2. Route the wire through the flex tubing to the associated zone satellite box. 3.

Strona 19

Removal and replacement procedures 26 ECS touchscreen The ECS touchscreen is located on the door to the control panel inside the cold aisle of the H

Strona 20 - Differential pressure sensor

Removal and replacement procedures 27 Replacing the ECS touchscreen 1. Replace the ESC touchscreen through the front of the door (1), and then secu

Strona 21

Removal and replacement procedures 28 Removing the EPO button 1. Remove the two screws securing the tamper cover (1), and then remove the tamper co

Strona 22 - Door position contact

Removal and replacement procedures 29 Replacing the EPO button 1. Replace the EPO button (1), and then replace the four screws that secure the EPO

Strona 23 - Drain pan sensor

Contents 3 Contents Illustrated parts catalog ...

Strona 24

Removal and replacement procedures 30 EPO LED indicators The ECS cabinet contains white (1, 3), red (2), yellow (4), and green (5) EPO LED indicator

Strona 25

Removal and replacement procedures 31 2. Unscrew the EPO LED indicator bulb. Replacing the EPO LED indicator 1. Screw the new EPO LED indicator b

Strona 26 - ECS touchscreen

Removal and replacement procedures 32 2. Push the module into the slot on the back of the ECS cabinet door until it clicks into place. EPO thermis

Strona 27 - EPO button

Removal and replacement procedures 33 2. Secure the thermister with tie wraps (2). External chilled water flow actuator The external chilled water

Strona 28 - Removing the EPO button

Removal and replacement procedures 34 2. Remove the four bolts securing the face plate (1), and then remove the face plate (2). 3. Disconnect the

Strona 29 - Replacing the EPO button

Removal and replacement procedures 35 Replacing the external chilled water flow actuator 1. Replace the actuator (1), and then secure the actuator

Strona 30 - EPO LED indicators

Removal and replacement procedures 36 Removing the external chilled water flow valve 1. Remove the external chilled water flow actuator. For detail

Strona 31

Removal and replacement procedures 37 External pressure gauge isolation valve The external pressure gauge isolation valve is located on top of the H

Strona 32 - EPO thermister

Removal and replacement procedures 38 Fan There are 18 fans per cooling zone. CAUTION: Power must be removed from the fan power assembly before

Strona 33

Removal and replacement procedures 39 2. Remove the three screws that secure the fan in the assembly (1), and then partially remove the fan by pulli

Strona 34

Contents 4 External pressure gauge isolation valve ...

Strona 35

Removal and replacement procedures 40 Fan bank There are three fan banks per cooling zone. CAUTION: Power must be removed from the fan power ass

Strona 36

Removal and replacement procedures 41 4. Remove the fan bank by pulling it straight out (3). Replacing the fan bank 1. Insert the fan bank (1). 2

Strona 37

Removal and replacement procedures 42 Fire strobe light The HP POD 40c G2 contains an internal fire alarm strobe light in the cold aisle and an exte

Strona 38 - Removing the fan

Removal and replacement procedures 43 Replacing the fire strobe light 1. Assemble the standard back box, the semi-flush plate, and the electric sou

Strona 39 - Replacing the fan

Removal and replacement procedures 44 Removing the humidifier 1. Hold the drain button on the humidifier exterior until the humidifier cylinder dra

Strona 40 - Fan bank

Removal and replacement procedures 45 10. Disconnect and remove the external electrical wiring from the housing (3). 11. Remove the four screws th

Strona 41 - Replacing the fan bank

Removal and replacement procedures 46 Replacing the humidifier 1. Replace the humidifier (1), and then secure the humidifier to the wall with four

Strona 42 - Fire strobe light

Removal and replacement procedures 47 6. Replace the humidifier cover (1), and then secure the cover with four screws (2). 7. Open the water suppl

Strona 43 - Humidifier

Removal and replacement procedures 48 2. Open and danger tag the associated circuit breaker in the ECS cabinet. The circuit breakers are identified

Strona 44 - Removing the humidifier

Removal and replacement procedures 49 a. Remove the screw securing the tab in the opening (1), and then slide the tab to the open position (2). b.

Strona 45

Contents 5 Rack specifications ...

Strona 46 - Replacing the humidifier

Removal and replacement procedures 50 Humidity sensor The HP POD 40c G2 contains two humidity sensors, one in cooling zone 2 and one in cooling zone

Strona 47 - Humidistat

Removal and replacement procedures 51 2. Loosen the sensor wires by turning the nut counter clockwise (1), remove the sensor wires from the terminal

Strona 48 - Replacing the humidistat

Removal and replacement procedures 52 Replacing the humidity sensor 1. Replace the sensor (1), and then secure the sensor with two screws (2). 2.

Strona 49

Removal and replacement procedures 53 3. Replace the sensor cover (1), and then secure the cover with four screws (2). LED light Each POD contains

Strona 50 - Humidity sensor

Removal and replacement procedures 54 2. Disconnect the LED light panel (2). Replacing the LED light 1. Connect the new LED light panel to the LE

Strona 51

Removal and replacement procedures 55 Temperature sensor (cold aisle) The HP POD 40c G2 contains six temperature sensors in the cold aisle. You nee

Strona 52

Removal and replacement procedures 56 3. For each of the five clamps securing the sensor tube to the HP POD 40c G2 structure, remove the screw that

Strona 53 - LED light

Removal and replacement procedures 57 3. Replace the sensor cover (1), and then secure the cover with two screws (2). Temperature sensor (hot aisl

Strona 54 - Replacing the LED light

Removal and replacement procedures 58 Removing the hot aisle temperature sensor 1. Remove the four screws that secure the sensor cover (1), and the

Strona 55

Removal and replacement procedures 59 3. Remove the two screws that secure the sensor (1), and then remove the sensor (2). Replacing the hot aisle

Strona 56

Illustrated parts catalog 6 Illustrated parts catalog Structural component identification The HP POD 40c G2 documentation frequently refers to the s

Strona 57

Removal and replacement procedures 60 2. Insert the sensor wire into the nut (1), secure the wire by turning the nut clockwise (2), and then insert

Strona 58

Removal and replacement procedures 61 Removing the VESDA filter 1. Remove the filter cover on the front of the VESDA unit. 2. Remove the 10mm screw

Strona 59

Removal and replacement procedures 62 2. Replace the VESDA filter cover.

Strona 60 - VESDA filter

Periodic maintenance 63 Periodic maintenance Periodic maintenance overview Perform periodic inspections on the components in this section to ensure

Strona 61 - Replacing the VESDA filter

Periodic maintenance 64 Component to be inspected Task Frequency Capable Party — Inspect for any water leaks and replace the cylinder if necessar

Strona 62

Periodic maintenance 65 Drains Component to be inspected Task Frequency Capable Party Drains Visually check drains for blockage Monthly Certif

Strona 63 - Periodic maintenance

Periodic maintenance 66 Component to be inspected Task Frequency Capable Party — Electrical panel, breaker, disconnect, and transformer visual in

Strona 64 - Leak detection maintenance

Periodic maintenance 67 Fire alarm and suppression system Component to be inspected Task Frequency Capable Party Full system functional check In

Strona 65 - Electrical

Periodic maintenance 68 HP POD 40c G2 structure Component to be inspected Task Frequency Capable Party Complete structure Visually inspect the s

Strona 66

Periodic maintenance 69 Component to be inspected Task Frequency Capable Party — Exterior water proofing check for ingress using water hose Annua

Strona 67 - Generator (if applicable)

Illustrated parts catalog 7 • Regulatory compliance identification number—This product has been assigned a unique regulatory model number and is lo

Strona 68 - Security

Specifications 70 Specifications General HP POD 40c G2 specifications Features Specifications Overall dimensions • Height—3.66 m (12 ft) • Lengt

Strona 69 - Third-party components

Specifications 71 Fire alarm panel connections The electrical layout of the fire alarm system is as described in the schematic drawing supplied with

Strona 70 - Specifications

Specifications 72 Feature Specification Non-operating temperature* -29ºC to 54ºC (-20ºF to 130ºF) Operating humidity • 0% to 100% external • 10%

Strona 71 - Environmental specifications

Contacting HP 73 Contacting HP Before you contact HP Be sure to have the following information available before you call HP: • Active Health System

Strona 72

Regulatory compliance notices 74 Regulatory compliance notices HP POD 40c G2 regulatory compliance The HP POD 40c G2 complies with the following reg

Strona 73 - Contacting HP

Regulatory compliance notices 75 • The HP POD 40c G2 meets the following ratings: Feature Specification Category Rated Overvoltage Category III P

Strona 74 - Safety and NEC compliance

Regulatory compliance notices 76 Regulatory requirements for EXIT signs Manufacturers of tritium EXIT signs are “specific licensees,” meaning they a

Strona 75 - Modifications

Glossary 77 Glossary branch circuit The conductors and components following the last overcurrent protective device protecting a load. control trans

Strona 76

Glossary 78 PDU power distribution unit PLC programmable logic controller power circuit Conductors and components of branch and feeder circuits.

Strona 77 - Glossary

Documentation feedback 79 Documentation feedback HP is committed to providing documentation that meets your needs. To help us improve the documentat

Strona 78 - Glossary 78

Illustrated parts catalog 8 Top view shown Item Component Description 1 Exit sign locations Indicates the location of an exit 2 Fire strobe lig

Strona 79 - Documentation feedback

Index 80 A air filter, removing 16 air filter, replacing 17 air filters 16 authorized reseller 73 B before you contact HP 73 busway drop b

Strona 80 - Index 80

Index 81 FCC (Federal Communications Commission) notice 75 Federal Communications Commission (FCC) notice 75 filter 16, 60 fire safety system

Strona 81 - Index 81

Index 82 standards 74 structural components 6 structure maintenance 68 switchgear maintenance 69 T technical support 73 telephone numbers

Strona 82 - Index 82

Illustrated parts catalog 9 Top view shown Power feeders IMPORTANT: A licensed electrician must connect the power according to all local and n