This subchapter pertains to all HP 9000 Superdome servers (running PA-8600, PA-8700 or PA-8800 processors) for all markets. With Superdome, HP
launches a new strategy to ensure a positive Total Customer Experience is achieved via industry-leading HP Services. Our experience has shown us that large
solution implementations most often succeed as a result of appropriate skills and attention being applied to the solution design and implementation. To
address this on the implementation side, for Superdome, HP is responding to Customer and Industry feedback and delivering Superdome Configurations via
three, pre-configured Services levels: Critical Service, Proactive Service and Foundation Service. With Superdome, we introduced a new role, the TCE
Manager, who manages the fulfillment of an integrated business solution based on customer requirements. For each customer account, the TCE Manager
will facilitate the selection of the appropriate configuration. For ordering instructions, please consult the ordering guide.
Superdome Service Solutions
Superdome Service SolutionsSuperdome Service Solutions
Superdome Service Solutions
Superdome continues to provide the same positive Total Customer Experience via industry leading HP Services as with existing Superdome servers. The HP
Services component of Superdome is described here:
Solution Life Cycle
Solution Life CycleSolution Life Cycle
Solution Life Cycle
HP customers have consistently achieved higher levels of satisfaction when key components of their IT infrastructures are
implemented using the
Solution Life Cycle
Solution Life CycleSolution Life Cycle
Solution Life Cycle
. The Solution Life Cycle focuses on rapid productivity and maximum
availability by examining customers' specific needs at each of five distinct phases (plan, design, integrate, install, and
manage) and then designing their Superdome solution around those needs.
QuickSpecs
HP 9000 Superdome Servers
HP 9000 Superdome ServersHP 9000 Superdome Servers
HP 9000 Superdome Servers
(PA-8600, PA-8700 and PA-8800)
(PA-8600, PA-8700 and PA-8800)(PA-8600, PA-8700 and PA-8800)
(PA-8600, PA-8700 and PA-8800)
Overview
DA - 11721 North America — Version 13 — April 1, 2005
Page 1
Przeglądanie stron 0
1 2 3 4 5 6 ... 43 44

Podsumowanie treści

Strona 1 - QuickSpecs

This subchapter pertains to all HP 9000 Superdome servers (running PA-8600, PA-8700 or PA-8800 processors) for all markets. With Superdome, HPlaun

Strona 2

Multi-system HighMulti-system HighMulti-system HighMulti-system HighAvailabilityAvailabilityAvailabilityAvailabilityAny Superdome partition with PA-RI

Strona 3

Supportability and management features on HP 9000 Superdome are covered in the next section. Service Processor (MP)Service Processor (MP)Service Proce

Strona 4

Support ManagementSupport ManagementSupport ManagementSupport ManagementStationStationStationStation (SMS)The Support Management Station (SMS) runs th

Strona 5

It is desirable, and sometimes essential for rapid time to repair to provide a reliable way to get console access that isphysically close to the serve

Strona 6

PA 8700PA 8700PA 8700PA 8700 Hardware RequirementHardware RequirementHardware RequirementHardware RequirementCustomers ordering an SMS for the first t

Strona 7

Console ConnectivityConsole ConnectivityConsole ConnectivityConsole ConnectivityPA8700 Superdomes require scan and console to be on separate networks.

Strona 8

Supports multiple, heterogeneous Superdome platforms.The Windows ProLiant SMS/Console is comprised of a ProLiant ML350 G3/G4 and a TFT5600 retractable

Strona 9

SMS/Console ConnectivitySMS/Console ConnectivitySMS/Console ConnectivitySMS/Console ConnectivityOne SMS can support up to 16 Superdomes using a switch

Strona 10

Mixed Superdome EnvironmentsMixed Superdome EnvironmentsMixed Superdome EnvironmentsMixed Superdome EnvironmentsSome important rules regarding SMS/Con

Strona 11

HP-UXHP-UXHP-UXHP-UXHP-UX Systems Insight ManagerHP-UX Systems Insight ManagerHP-UX Systems Insight ManagerHP-UX Systems Insight Manager is an easy-to

Strona 12

Service SolutionsService SolutionsService SolutionsService SolutionsHP offers three pre-configured service solutions for Superdome that provide custom

Strona 13

OpenView Operations AgentOpenView Operations AgentOpenView Operations AgentOpenView Operations Agent-collects and correlates OS and application events

Strona 14

Console ConsiderationsConsole ConsiderationsConsole ConsiderationsConsole ConsiderationsThe optimal configuration of console device(s) depends on a nu

Strona 15

Pre-existing SMSPre-existing SMSPre-existing SMSPre-existing SMSCustomersCustomersCustomersCustomersSome customers may have an existing rp2470 or A500

Strona 16

Cooling RequirementsCooling RequirementsCooling RequirementsCooling RequirementsThe cooling system in Superdome was designed to maintain reliable oper

Strona 17

Uninterruptible PowerUninterruptible PowerUninterruptible PowerUninterruptible PowerSupplies (UPS)Supplies (UPS)Supplies (UPS)Supplies (UPS)HP will be

Strona 18

Power ProtectionPower ProtectionPower ProtectionPower ProtectionRuntimesRuntimesRuntimesRuntimesThe UPS will provide battery backup to allow for a gra

Strona 19

Power ManagementPower ManagementPower ManagementPower ManagementDescriptionDescriptionDescriptionDescriptionNetwork interface cards that provide stand

Strona 20

SuperDome Configuration Guidelines/RulesSuperDome Configuration Guidelines/RulesSuperDome Configuration Guidelines/RulesSuperDome Configuration Guidel

Strona 21

CategoryCategoryCategoryCategoryRule IndexRule IndexRule IndexRule IndexRule DescriptionRule DescriptionRule DescriptionRule DescriptionPerformancePer

Strona 22

CategoryCategoryCategoryCategoryRule IndexRule IndexRule IndexRule IndexRule DescriptionRule DescriptionRule DescriptionRule DescriptionSingle SystemS

Strona 23

NOTE:NOTE:NOTE:NOTE: Given that PA-8600/PA-8700 are single-core processors and PA-8800 is a dual-core processor, the columns listed in this table refe

Strona 24

CategoryCategoryCategoryCategoryRule IndexRule IndexRule IndexRule IndexRule DescriptionRule DescriptionRule DescriptionRule DescriptionMulti-SystemMu

Strona 25

Power RedundancyPower RedundancyPower RedundancyPower RedundancySuperdome servers, by default, provide an additional power supply for N+1 protection.

Strona 26

individually. DescriptionDescriptionDescriptionDescriptionProduct NumberProduct NumberProduct NumberProduct NumberPA-8800 processor assembly (conta

Strona 27

of a true utility model in a capitalized version.To order Temporary Instant Capacity apacity on Superdome, A7067A must be ordered. For more informatio

Strona 28

For information on Superdome Server Upgrades, please refer to the Superdome Server Upgrades QuickSpec.QuickSpecsHP 9000 Superdome ServersHP 9000 Super

Strona 29

Superdome SpecificationsSuperdome SpecificationsSuperdome SpecificationsSuperdome SpecificationsSPU DescriptionSPU DescriptionSPU DescriptionSPU Descr

Strona 30

HP-UX AttributesHP-UX AttributesHP-UX AttributesHP-UX AttributesMaximum CPUs per HP-UX 11ipartition16 32 64Maximum CPUs per HP-UX 11ipartition16 32 12

Strona 31

Regulatory ComplianceRegulatory ComplianceRegulatory ComplianceRegulatory ComplianceSafetyIEC 950:1991+A1, +A2, +A3, +A4; EN60950:1992+A1, +A2, +A3,

Strona 32

Superdome I/O ExpansionSuperdome I/O ExpansionSuperdome I/O ExpansionSuperdome I/O Expansion(IOX) Cabinet(IOX) Cabinet(IOX) Cabinet(IOX) CabinetSpecif

Strona 33

ManagementIncludesIncludesIncludesIncludesParallel Card, Triple Chassis for three SmartSlots, User Manual, Web/SNMP ManagementCardSpare parts kitsSpar

Strona 34

There are three basic building blocks in the Superdome system architecture: the cell, the crossbar backplane and the I/O subsystem. Please note thatSu

Strona 35

* Without TAX/VAT** The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the fullload ra

Strona 36

X.21PCI 8 port X.25/BX.25 AdvanceCommunications ControllerZ7340A RS-232, V.35,RS-449 or X.2125 25 25 Additional Interface CardsAdditional Interface

Strona 37

CopperPCI-X 133MHz 10GbE SR Fiber AdapterAB287A 16 32 64 PCI-X 4-port 1000 Base-T GigabitAdapterAB545A 16 32 64 PCI -X 24 port 4x Fabric Coppe

Strona 38

C7508AZ (racked TA5300 tape and DVD chassis)C1354AZ (racked TA5500 tape chassis)Mass Storage InfrastructureMass Storage InfrastructureMass Storage Inf

Strona 39

© Copyright 2005 Hewlett-Packard Development Company, L.P.The information contained herein is subject to change without notice.Microsoft and Windows S

Strona 40

Cells (CPUs and Memory)Cells (CPUs and Memory)Cells (CPUs and Memory)Cells (CPUs and Memory)A cell, or cell board, is the basic building block of a Su

Strona 41

I/O SubsystemI/O SubsystemI/O SubsystemI/O SubsystemEach I/O chassis provides twelve I/O slots. Superdome PA-8600 and Superdome PA-8700 support I/O ch

Strona 42

Factory IntegrationFactory IntegrationFactory IntegrationFactory IntegrationWhen an I/O Expansion cabinet is ordered as an upgrade to a Superdome syst

Strona 43

DVD SolutionDVD SolutionDVD SolutionDVD SolutionThe DVD solution for Superdome requires the following components per partition. External racks A4901A

Strona 44

High AvailabilityHigh AvailabilityHigh AvailabilityHigh AvailabilityNOTE: NOTE: NOTE: NOTE: Online addition/replacement for cell boards is not current