Hardware options installation 59
7. Install fan modules 1 and 2 ("Remove and install a fan module" on page 23).
8. Install the air baffle ("Remove and install the air baffle" on page 20).
9. Install the access panel (on page 20).
10. Slide the server into the rack.
11. Power up the server (on page 18).
Using a PCI SAS or SATA array controller to support six hard
drives
1. Power down the server (on page 18).
2. Extend the server from the rack (on page 19).
3. Remove the access panel (on page 20).
4. Remove the air baffle ("Remove and install the air baffle" on page 20).
5. Remove fan modules 1 and 2 ("Remove and install a fan module" on page 23).
6. Disconnect all cables from the currently-installed HP Smart Array E200i Controller or HP Smart Array
P400i Controller.