Web interface 13
Solution:
1. View the Overview menu to distinguish which temperature sensor is different from the other
temperature sensors.
2. After discovering which temperature sensor is not working properly, remove that module and
reinstall it. If the difference is in the Server Exhaust Temperature, replace the appropriate fan unit. If
the difference is in the Server Intake Temperature, replace the appropriate HEX unit.
If the warning message does not clear after the module is reseated, replace the HEX unit with a CSR part.
For more information on CSR parts, see "Replaceable parts and maintenance and service information (on
page 55)."
Low water flow
Indicators Meaning
Actual operator display alarm
message
Water flow Low
Actual web interface alarm
message
Water flow Low
Condition No or low water flow
Modules Water group
SNMP notification Warning
Type of message Warning
Solution:
Verify the water supply.
Water temperature input is out of range
Indicators Meaning
Actual operator display alarm
message
Water Temp. In Failed
Actual web interface alarm
message
Water Unit Temperature Input Out of Range
Condition Water temperature sensor is not working properly (possible open circuit)
Sensors Water group sensor
SNMP notification Warning
Type of message Warning
Solution:
1. Verify the water supply.
2. Verify whether the water temperature is below or above the water temperature expected range.
3. Contact your building supervisor.
4. Contact HP, or see the HP website (http://www.hp.com).
Water temperature output is out of range