HP Advanced Power Manager
User Guide
Abstract
This guide provides installation and operation guidance for the HP Advanced Power Manager. This guide is for the person who i
nstalls, administers,
and troubleshoots servers and storage systems.
Part Number: 747697-001
June 2014
Edition: 1
Przeglądanie stron 0
1 2 3 4 5 6 ... 116 117

Podsumowanie treści

Strona 1 - User Guide

HP Advanced Power Manager User Guide Abstract This guide provides installation and operation guidance for the HP Advanced Power Manager. This guide

Strona 2

Introduction 10 HP APM front view Item Description 1 Consolidated Management Ports 1 through 10 (RDM1) 2 Power LED 3 Serial management for top of

Strona 3 - Contents

Supported MIB objects 100 Supported MIB objects Supported cpqRack MIB objects Object name Object identifier Notes Compaq 1.3.6.1.4.1.232 — cpqRa

Strona 4 - Contents 4

Supported MIB objects 101 Object name Object identifier Notes cpqRackCommonEnclosureSerialNumPrev 1.3.6.1.4.1.232.22.2.3.1.1.1.24 — cpqRackCommon

Strona 5 - Contents 5

Supported MIB objects 102 Object name Object identifier Notes cpqRackServerBlade 1.3.6.1.4.1.232.22.2.4.1 — cpqRackSystemTime 1.3.6.1.4.1.232.22.

Strona 6 - Contents 6

Supported MIB objects 103 Object name Object identifier Notes exception of HP ProLiant s6500 Chassis cpqRackEnclosureFanInserted 1.3.6.1.4.1.232.2

Strona 7 - Contents 7

Supported MIB objects 104 Object name Object identifier sysContact 1.3.6.1.2.1.1.4 sysName 1.3.6.1.2.1.1.5 sysLocation 1.3.6.1.2.1.1.6 sysServices

Strona 8 - Introduction

Supported MIB objects 105 Object name Object identifier ifNumber 1.3.6.1.2.1.2.1 ifNumber 1.3.6.1.2.1.2.1 ifTable 1.3.6.1.2.1.2.2 ifEntry 1.3.6.1.2

Strona 9 - HP APM kit contents

Supported MIB objects 106 Object name Object identifier ipReasmFails 1.3.6.1.2.1.4.16 ipFragOKs 1.3.6.1.2.1.4.17 ipFragFails 1.3.6.1.2.1.4.18 ipFra

Strona 10 - HP APM front view

Supported MIB objects 107 Object name Object identifier ipRoutingDiscards 1.3.6.1.2.1.4.23 ipInReceives 1.3.6.1.2.1.4.3 ipInHdrErrors 1.3.6.1.2.1.4

Strona 11 - HP APM connections

Supported MIB objects 108 Object name Object identifier icmpInEchoReps 1.3.6.1.2.1.5.9 tcp 1.3.6.1.2.1.6 tcpRtoAlgorithm 1.3.6.1.2.1.6.1 tcpInSegs

Strona 12 - Item Component Connects To

Supported MIB objects 109 PDU identity table Two new tables are supported in the PDU section of the CPQ POWER MIB. These two tables are supported fo

Strona 13 - Identifying the RDM1 ports

Introduction 11 HP APM rear view Item Description 1 Power plugs 1 and 2 2 On-Generator and AUX signals 3 Redundant reset HP APM connections HP

Strona 14 - • HP Moonshot System

Regulatory information 110 Regulatory information Safety and regulatory compliance For safety, environmental, and regulatory information, see Safety

Strona 15

Regulatory information 111 Valid date formats include the following: • YWW, where Y indicates the year counting from within each new decade, with 2

Strona 16 - Using RJ-45 connections

Support and other resources 112 Support and other resources Before you contact HP Be sure to have the following information available before you cal

Strona 17 - Rack chassis numbering

Acronyms and abbreviations 113 Acronyms and abbreviations CM chassis management DHCP Dynamic Host Configuration Protocol FQDN Fully Qualified Doma

Strona 18 - Automatic discovery

Documentation feedback 114 Documentation feedback HP is committed to providing documentation that meets your needs. To help us improve the documenta

Strona 19 - Introduction 19

Index 115 A ADD ACCOUNT 76 ADD ZONE 56, 88 alert messages 74 authorized reseller 112 automatic discovery 18 B before you co

Strona 20 - Configuring the HP APM

Index 116 command, SHOW CONFIG 59, 84 command, SHOW FAULTS 32, 35, 84 command, SHOW INFO 60, 84 command, SHOW KEYS 69, 92 comman

Strona 21

Index 117 P password settings 54, 55 passwords 54, 55, 58 PDU identity table 109 PDU input table 109 phone numbers 112 powe

Strona 22 - Network configuration

Introduction 12 Depending on the product being connected to the HP APM, the HP APM connects to the system components using various cables. All cable

Strona 23 - Protocol configuration

Introduction 13 Item Component Connects To 10 Terminal Serial console port on the HP APM 11 RDM • RDM2 or RDM3 port on the HP APM • RDM/HP APM*

Strona 24 - Command Line Interface

Introduction 14 Identifying the RDM2 and RDM3 ports Consolidated management ports (RDM1) are used only for products designed to work with HP APM whe

Strona 25 - Topology and inventory

Introduction 15 Item Description 1 Connector port to the RDM2 or RDM3 ports on HP APM 2 SL Scalable Series server connectors 3 Power (green) LED,

Strona 26 - Command Line Interface 26

Introduction 16 Using RJ-45 connections You can have one HP APM per power network (one CLI interface over an Ethernet). One HP APM can connect up to

Strona 27 - Command Line Interface 27

Introduction 17 Item Description 3 HP ProLiant SL Series Chassis 4 HP Moonshot 1500 Chassis 5 Power Distribution Unit 6 HP Intelligent Modular PDU

Strona 28 - Showing topology

Introduction 18 Item Description 3 Connections to SL series enclosures The HP APM commands SHOW TOPOLOGY and SHOW RACK displays the SL chassis con

Strona 29 - Showing assetinfo

Introduction 19 The discovery process also has a simple fault detection mechanism. If any node has faults detected (for example, power supply failur

Strona 30 - Showing the MAC address

© Copyright 2014 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties

Strona 31 - Command Line Interface 31

Installation and configuration 20 Installation and configuration Prerequisites for installation The HP APM can be administered through the serial co

Strona 32 - Logging

Installation and configuration 21 • Duplicate the configuration. For more information, see "Duplicating the configuration (on page 23)."

Strona 33 - Logging 33

Installation and configuration 22 Serial port configuration Verify that the client matches the following settings: • Baud rate115200 • Data bits

Strona 34 - Logging 34

Installation and configuration 23 Security configuration The network interface is disabled when password protection is removed. For more information

Strona 35 - HP APM fault messages

Command Line Interface 24 Command Line Interface Command line conventions CLI input is case insensitive except when otherwise noted. The CLI uses a

Strona 36

Command Line Interface 25 2. When prompted, enter the assigned IP address or FQDN name of HP APM. 3. Enter Administrator. 4. Enter a valid passwor

Strona 37 - Working with RADIUS servers

Command Line Interface 26 6 : Compute node (active) 7 : Compute node (active) 8 :

Strona 38 - Showing a RADIUS server

Command Line Interface 27 1 : Compute node (active) 2 : Compute node (active) 3 :

Strona 39 - Power capping

Command Line Interface 28 Serial Number: ADFV0000083 Asset Tag : SCI Lab PDU Part Number : QL192A Firmware Rev : 1.0a Switch

Strona 40 - Rack level power capping

Command Line Interface 29 Showing assetinfo To list all the chassis in the rack in a report format, enter SHOW ASSETINFO. For example, the following

Strona 41 - Power baseline

Contents 3 Contents Introduction ...

Strona 42 - Power capping 42

Command Line Interface 30 2: enabled 3: enabled 4: enabled 5: enabled 6: enabled Input Feeds: 1:

Strona 43 - Setting power capping

Command Line Interface 31 Fan slot 7 status good Fan slot 8 status good To show a particular MAC address,

Strona 44 - Power capping 44

Logging 32 Logging Overview of logging Logging enables you to see the following information in HP APM: • Actions taken • Events • Time when the a

Strona 45 - Power capping 45

Logging 33 Nov 6 11:51:25 SLAPM system.0: Server found in chassis at Dist. Module #2, port 3, slot 8 Nov 6 11:51:25 SLAPM system.0: Power supply

Strona 46 - Power capping 46

Logging 34 Nov 6 11:51:26 SLAPM system.0: Server found in chassis at Dist. Module #2, port 6, slot 7 Nov 6 11:51:26 SLAPM system.0: Server found i

Strona 47

Logging 35 Showing and clearing the fault log To show the fault log, enter SHOW FAULTS. As an example, the following text might appear on screen: &g

Strona 48 - Power capping with zones

Logging 36 Fault logged message Description Fans: • Power Manager Fan 2, failed • Both fans failed • One or more Fan rotor(s) failed • One or m

Strona 49 - Power commands

Logging 37 XML-related fault messages The following XML-related fault messages might appear in your fault log: • Failed to allocate memory for XML

Strona 50

Logging 38 Showing a RADIUS server To show the currently configured RADIUS server, enter SHOW RADIUS. To show the currently configured RADIUS parame

Strona 51 - Setting power

Power capping 39 Power capping Power capping overview HP Scalable System products, including HP ProLiant SL Series, HP Moonshot Series, and HP Apoll

Strona 52 - Power capping 52

Contents 4 Showing a RADIUS server ...

Strona 53 - Power capping 53

Power capping 40 installed), then the HP APM detects this change and invalidates the current power baseline. This invalidation prevents any new caps

Strona 54 - General commands

Power capping 41 Power baseline The power baseline is a calibration that indicates the range of how little power the chassis can consume at their ma

Strona 55 - Working with accounts

Power capping 42 To remove baseline data from the EEPROM, use the SET POWER BASELINE NONE command. After this command is used, the only way to re-es

Strona 56 - Working with zones

Power capping 43 Setting power capping Use the SET POWER CAP command to specify a power cap. The command takes an AC wattage range that must be betw

Strona 57 - General commands 57

Power capping 44 1 3 2 257 n/a 340 (DC watts) 1 3 3 242 n/a 324 (DC watts) 1 3

Strona 58 - Using password recovery

Power capping 45 ---- 718 The following example uses the power distribution module. > show power pdm PDM port 1

Strona 59 - Setting the name

Power capping 46 Total system wattage = 2033 (DC watts) Total system wattage = 2148 (AC watts) > show power baseline All values listed are in AC

Strona 60 - Showing information

Power capping 47 3 (no Dist. Module present) 4 (no Dist. Module present) 5 (no Dist. Module present) 6 (no Dist. Module pres

Strona 61 - Showing the version

Power capping 48 Defining zones is an optional function, and is useful for applying power caps to some chassis while excluding others or applying di

Strona 62 - General commands 62

Power capping 49 APMPort DMPort Serial Number Min Cap Max Cap Set Cap Slots Populated ------- ------ ------------- ------- ------- ------- -----

Strona 63 - Connecting and setting ports

Contents 5 SNMP overview ...

Strona 64 - Using SNMP

Power capping 50 In the following figure, the HP APM port 2 is connected to the HP APM Distribution Module port 4. The distribution module port is c

Strona 65 - Setting the SNMP location

Power capping 51 • A total count of all the servers and chassis listed • Total fan wattage for the listing • Total system wattage in DC watts •

Strona 66 - Using SNMP 66

Power capping 52 To turn an SL server node on or off, use the SET POWER command: SET POWER {ON|OFF|ENABLE|DISABLE} {ALL | <PORT#> <DMPORT#&

Strona 67 - Using XML

Power capping 53 Disabling the polling of servers for power values To disable the background process that is polling each server for power usage, en

Strona 68 - Response definitions

General commands 54 General commands Working with passwords HP APM has a password recovery mechanism through the reset switch. If you press the rese

Strona 69 - Modifying the user account

General commands 55 When entering a password in this manner, you must include quotation marks around the password being set. This form of command is

Strona 70 - Modifying compute node power

General commands 56 Account MyLogin123 enabled myslapm> The account name must be between2-32 characters. If you attempt to use more than 32 chara

Strona 71 - Resetting HP APM

General commands 57 ADD ZONE <zone_name> [[<PORT#> <DMPORT#>]] | [<PORT#> ALL] | [ALL] where: • <zone_name> is the z

Strona 72 - Using XML 72

General commands 58 Removing zones To remove one or more chassis from a zone definition, enter REMOVE ZONE <zone_name> [[<PORT#> <DMP

Strona 73 - Firmware

General commands 59 Showing configurations To show the configuration, enter SHOW CONFIG. A list of commands representing the configuration of HP APM

Strona 74 - Troubleshooting

Contents 6 Reset ...

Strona 75 - CLI commands

General commands 60 the power manager name, press Enter. Naming the HP APM is optional. This is the name that appears in log entries on the syslog s

Strona 76 - CLI commands 76

General commands 61 • Serial Number • FRU File ID The power manager is the bottom board, and the connector module is the top board that has all th

Strona 77 - Set password account

General commands 62 For example, the following text appears: APM-D4C9EFCB00B4> show version HP Advanced Power Manager (c) Copyright 2014 Hewlett

Strona 78 - • Command:

General commands 63 All configuration and password settings will be lost. Password access will be disabled. Network access will be prevented due to

Strona 79 - CLI commands 79

Using SNMP 64 Using SNMP SNMP overview The architectural model for SNMP contains these components: • At least one network management station with m

Strona 80 - Save config

Using SNMP 65 Setting the SNMP read-only community string To set the SNMP read-only community string, enter SET SNMP RO "<community_string&g

Strona 81 - Set power

Using SNMP 66 • cpqRackPowerSupplyOK • cpqRackPowerSupplyRemoved • cpqRackPowerSupplyInserted • cpqRackServerBladeRemoved • cpqRackServerBladeI

Strona 82 - Set timeout

Using XML 67 Using XML XML overview XML scripting provides a standard programmatic means for data center tools to interact with the HP APM. You can

Strona 83 - Set asset info

Using XML 68 Response definitions Every command sent to HP APM generates a response. The response tells whether the command succeeded or failed. Som

Strona 84 - CLI commands 84

Using XML 69 MSG This element contains a message describing the error that occurred. If no error occurred, the message No error appears. Depending o

Strona 85 - Show rack

Contents 7 Reset keys ...

Strona 86 - Show asset info

Using XML 70 <LOGIN USER_LOGIN="Administrator" PASSWORD="password"> <USER_INFO> <MOD_USER USER_LOGIN="Admini

Strona 87 - Upgrade image

Using XML 71 <MOD_COMPUTE_NODE_POWER> <SLAPM PORT=”1”/> <DIST_MODULE PORT=”1”/> <NODE PORT=”1”/> <STATUS VALUE=”ON”/>

Strona 88 - Add zone

Using XML 72 For example: <SLAPMCL VERSION="2.00"> <LOGIN USER_LOGIN="Administrator" PASSWORD="password">

Strona 89 - Disable pollpower

Firmware 73 Firmware Upgrading the firmware You can perform firmware upgrades using either FTP or TFTP. To perform an upgrade: 1. Place the firmwar

Strona 90 - Set SNMP RW

Troubleshooting 74 Troubleshooting Alert messages The following messages appear in HP APM. Message Where this issue occurs Required action There

Strona 91 - Set SNMP trapdest

CLI commands 75 CLI commands Clear faults • Command: CLEAR FAULTS • Description: Clears the fault log to have 0 entries. Clear log • Command: CL

Strona 92 - Reset keys

CLI commands 76 Enables network access. Requires a password to be set and enabled. SSH and Telnet access must be enabled or disabled separately. Als

Strona 93 - CLI commands 93

CLI commands 77 NOTE: Only an Administrator can add or enable a new user account. • Command: ADD ACCOUNT "<username>" • Descr

Strona 94 - Show NTP server

CLI commands 78 • Description: o Configures the Administrator account password. Until a password is set, both Telnet and SSH are disabled. The pas

Strona 95 - Set port

CLI commands 79 Same as LOGOUT. Help • Command: HELP • Description: Displays a list of available commands. Logout • Command: LOGOUT • Descript

Strona 96 - XML commands

Introduction 8 Introduction HP APM overview HP APM is a rack-level point of contact for HP ProLiant Scalable System and HP Apollo administration. Fo

Strona 97 - Modify compute node power

CLI commands 80 • Description: Same as RESET. Reboot CM • Command: REBOOT CM <PORT#> <DMPORT#> where: <PORT#> refers to the HP

Strona 98 - Get compute node

CLI commands 81 Set IP • Command: SET IP {DHCP | <IP_ADDRESS> <IP_MASK>} • Description: Assigns static IP address and subnet mask or c

Strona 99 - Reset HP APM

CLI commands 82 Set serial • Command: SET SERIAL <baud rate> • Description: o Configure the serial console baud rate. o Serial access to t

Strona 100 - Supported MIB objects

CLI commands 83 SET TIMEOUT 30 If you specify NONE, then no session timeouts are set. For example, enter: SET TIMEOUT NONE • Description: Sets the

Strona 101

CLI commands 84 Show accounts • Command: SHOW ACCOUNTS • Description: Shows the existing defined accounts, including the reserved Administrator ac

Strona 102

CLI commands 85 Shows the current syslog IP address configuration. This command does not show the actual contents of the syslog. Show name • Comma

Strona 103

CLI commands 86 Show servers • Command: SHOW SERVERS SHOW SERVERS <PORT#> SHOW SERVERS <PORT#> <DMPORT#> where: <PORT#> ref

Strona 104

CLI commands 87 Show MAC address • Command: SHOW MACADDR SHOW MACADDR <PORT#> SHOW MACADDR <PORT#> <DMPORT#> where: <PORT#>

Strona 105

CLI commands 88 UPGRADE IMAGE TFTP <ip_address> "<filename>" o If using FTP protocol for upgrading HP APM, enter: UPGRADE IMA

Strona 106

CLI commands 89 Save zones • Command: SAVE ZONES • Description: o Commits the defined zones and their member chassis to the on-board EEPROM. o

Strona 107

Introduction 9 HP APM kit contents Item Description 1 HP APM 2 Mounting brackets (2) 3 Terminal blocks (2) 4 Power cords (2) 5 Bracket mountin

Strona 108

CLI commands 90 DISABLE POLLPOWER • Description Disables background process that polls each server for power usage. Enable SNMP • Command: ENABLE

Strona 109 - PDU input table

CLI commands 91 Set SNMP contact • Command: SET SNMP CONTACT "<sysContact>" • Description: Sets the MIB II sysContact field. Set

Strona 110 - Regulatory information

CLI commands 92 — cpqRackServerBladeInserted Enable XML • Command: ENABLE XML • Description: Turns on XML interface and makes XML queries availa

Strona 111 - Warranty information

CLI commands 93 Add RADIUS server • Command: ADD RADIUS SERVER <ip_address> <shared_secret> • Description: Specifies an initial, or ad

Strona 112 - Support and other resources

CLI commands 94 SET RADIUS POLLNUM • Description: Number of times HP APM polls each of the radius server indicated in the ADD RADIUS SERVER command

Strona 113 - Acronyms and abbreviations

CLI commands 95 Show NTP poll • Command: SHOW NTP POLL <poll_time_in_minutes> • Description: Indicates the time in minutes to poll for time

Strona 114 - Documentation feedback

XML commands 96 XML commands Login • Command: <LOGIN USER_LOGIN="username" PASSWORD="password"> </LOGIN> where USER

Strona 115 - Index 115

XML commands 97 <SLAPMCL VERSION="2.00"> <LOGIN USER_LOGIN="Administrator" PASSWORD="password"> <GET_FW

Strona 116 - Index 116

XML commands 98 <SLAPMCL VERSION="2.00"> <LOGIN USER_LOGIN="Administrator" PASSWORD="password"> <MOD_CO

Strona 117 - Index 117

XML commands 99 </GET_COMPUTE_NODE_POWER> </LOGIN> </SLAPMCL> where USER_LOGIN is the login name of the user account. This paramet