Facility planning for implementation 43
Voltage fluctuations and outages
The MCS-200/100 is designed to provide immunity to power outages of less than one cycle. However,
testing cannot conclusively rule out loss of service. To obtain the best possible performance of power
distribution systems for HP equipment, observe the following guidelines:
Dedicated power sourceIsolates the power distribution system from other circuits in the facility
Missing-phase and low-voltage detectorsAutomatically shuts down equipment when a severe power
disruption occurs. For peripheral equipment, these devices are recommended but optional.
Online UPSMaintains constant input voltage for devices and should be considered if outages of
one-half cycle or more are common. For each situation, consult a qualified contractor or consultant.
You can protect the MCS-200/100 from the sources of many electrical disturbances by using:
An isolated power distribution system
Power conditioning equipment
Over- and under-voltage detection and protection circuits
Protection to reduce high-frequency electrical energy radiation
Surge protective devices on power cables to protect equipment against electrical storms
Electrical planning around water-handling components
CAUTION: In case water is in contact with the power cables, shut down the main breaker before
cleaning up water in this area.
Because of potential condensation on non-insulated water connections or leaking water connections around
water-based cooling systems, consider the following during the electrical planning:
Waterproofed connectors
Watertight conduits for cables
Leak detection systems
To identify waterproofed connectors, HP recommends that you use the IP rating of the connector based on the
international standard IEC 60529. HP recommends a connector that is rated at least IP 67.
Cable conduits are available in different styles, depending on flexibility and materials. The most common
materials are plastic, metal, nylon, or a composition of these materials. Watertight conduits are available in
both flexible and hard material, depending on the application.
A leak detection system for a data center usually uses leak sensor cables, which are installed on the subfloor
in a raised floor and connected to a facility management system.
Connecting to facility A/C power
The MCS-200/100 accepts AC power through two Walther Procon A5 series power receptacles located at
the top rear patch panel. If available, the MCS-200 ships with one of each AC power cord set for connecting
to redundant AC power busses. The NEMA L6-20 power cord uses a NEMA L6-20 male plug for connecting
to a facility AC feed connector common to North America and Japan. The IEC 309 power cord uses an IEC
309 male plug for connecting to a facility AC feed connector common in various international regions.
These redundant connections and cords are optional for the MCS-100.