Facility planning for implementation 44
MCS-200/100 power L6-20 connector
MCS-200/100 IEC 309 power connector
At least one power cord must be used for MCS-200/100 operation. To improve system availability, the
second cord can connect to a redundant AC power bus (optional for the MCS-100). When the redundant
power is connected, the transfer switch assembly of the MCS-200/100 provides switch-over to the active
power bus, in the event of power source failures or accidentally tripped circuit breakers.
The power cords of the MCS-200/100 are 4 m (13.1 ft) long. The power connections are inside of the top
of the IT rack as shown in the following figures.