Each of the two PDU power cables has an AC power source specic connector. The circuit
breaker-controlled PDU outputs are routed to a group of four AC receptacles (see Figure 31). The
voltages are then routed to PDMs, sometimes referred to as AC power strips, m ounted on the two vertical
rails in the rear of the rack.
1
0130a
2
3
5
4
5
Figure 31 D
ual PDU assembly
1. PDU 1
2. PDU 2
3. Circuit
breakers
4. AC recep
tacles
5. Mounting hardware
PDU 1
PDU 1 conn
ects to AC power distribution source 1 . A PDU 1 failure:
Disables the power distribution circuit.
Removes power from PDMs 1, 2, and 3.
Disable
sPS1inthedriveenclosures.
Disables the upper controller power supply.
PDU 2
PDU 2 connects to AC power distribution source 2. A PDU 2 failure:
Disables the power distribution circuit.
Removes power from PDMs 4, 5, and 6.
Disables PS 2 in the drive enclosures.
Disables the lower controller power supply.
PDMs
There are six PDMs mounted in the rear of ea ch rack:
Three mo unted on the left vertical rail connect to PDU 1 .
Three
mounted on the right vertical rail connected to PDU 2.
Each PDM has eight AC receptacles and one thermal circuit breaker. The PDMs d istribute the AC power
from the PDUs to the enclosures. Two power sources exist for each controller pair and drive enclosure. If
a PDU fails, the system will remain operational.